Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2015 MARTIN BROWN FIRE REVIEW Approved
07/06/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the dimensions for the new scupper and downspout. Provide overflow protection for the roof. Reference: Section 107.2.1, IBC 2012; Sections 1101, 1106 and 1108, IPC 2012.
07/06/2015 ROBERT SHERRY WATER REVIEW Completed
07/06/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/07/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed
07/10/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1. Please provide a complete fault current analysis for the service and downstream equipment.
#2. Provide for all exterior lighting to be in compliance with the Tucson Outdoor Lighting Code. Per sec. 106.2.1, 402.1.
#3. Provide complete panel schedules for all panels.

Additional comments may be generated after subsequent review due to insufficient information to perform a complete and code compliant review at this time.