| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/06/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the dimensions for the new scupper and downspout. Provide overflow protection for the roof. Reference: Section 107.2.1, IBC 2012; Sections 1101, 1106 and 1108, IPC 2012. |
| 07/06/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/06/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 07/07/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 07/10/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1. Please provide a complete fault current analysis for the service and downstream equipment. #2. Provide for all exterior lighting to be in compliance with the Tucson Outdoor Lighting Code. Per sec. 106.2.1, 402.1. #3. Provide complete panel schedules for all panels. Additional comments may be generated after subsequent review due to insufficient information to perform a complete and code compliant review at this time. |