Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T15CM03859
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2015 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T15CM03859 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. FLOOR PLANS: 1. Update notation (sheet A-2.1) showing compliance with R310 providing egress from bedroom #1. A minimum net clear opening width of 48" is not provided with a 4040 slider. The actual opening is less than 24" considering the window framing reduces the rough-in opening. The 4040 slider window will pass although the notation is misstated. ELEVATIONS: 1. Provide consistent information for the unvented (insulation filled) rafter space, R806. Remove the vent area calculation and venting notation (sheet A-3) when not providing a minimum 1" clear space between the insulation and roof sheathing. 2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with additional insulation types for meeting the condensation control requirement. 3. Show a roof design with a total insulation value of R-30 when the insulation layers are extended over the wall top plates; or show overall compliance if using less than prescribed component values by providing a RES check calculation, N1102.1. PLUMBING PLANS: 1. Clarify keynotes #17. Notes #3 - 14 are shown at two locations. ELECTRICAL PLANS: 1. Only the 15A & 20A outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors are required to be combination type arc-fault circuit interrupters, E3902.12. Update the note at the upper right corner of sheet A-5. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/13/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |