Permit Number: T15CM03844
Parcel: 137291840

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM03844
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM03844
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

1. Provide two sets of plans showing compliance with City of Tucson adopted building codes. The 2012 IRC with amendments was adopted on 1/1/2012.
2. Items built without permit may require alteration or improvement for achieving code compliance with the 2012 IRC, R101.3.
3. Include construction details for the garage area changed into living space.

SITE PLAN:

1. Indicate the location of utility meters and gas, water, electric and sewer lines from property line to building, R106.1.1.

STRUCTURAL PLANS:

1. Clarify the porch framing plan, sheet G-6, with rafters at 24" OC (on-center) spacing rather than as wood beams, R301.1.3.

SECTIONS - DETAILS:

1. Provide a complete cross-section detail from foundation to roof assembly for each type of exterior wall needing permit, R106.1.1.
2. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground (R317.1 item 5) with treated sill plates, R602.10.8 & R403.1.6.
3. Notate or detail interior wall and ceiling covering (1/2" GWB), R702.3 and R-30 ceiling and R=13 wall insulation within exterior framing spaces, N1102.1.

PLUMBING PLANS:

1. Show a plumbing plan for the laundry room, or change the storage room on the original plan to laundry room.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.9. Show the size and location of the heating and cooling system with supply and return ducts to the new rooms.

ELECTRICAL PLANS:

1. Show locations of each smoke alarm, R314. Smoke alarms are required inside bedrooms and outside each separate sleeping area, R314.3.2.
2. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.3.1. Provide notation if existing or proposed.
3. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.12 & E3706.2. Remove the electrical consumption calculator information form the plans, sheet G-4.
4. Show the location of the service panel on the plans, E3601.6.2 & E3705.8.
5. Show receptacle outlets at each wall space in master living room and bedroom #4 with no wall point (exclude door openings) more than 6' from a receptacle outlet, E3901.2. That is within 6 feet of the doors and not more than 12 feet apart.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/02/2015 KROBLES1 OUT TO CUSTOMER Completed