Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03795
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/05/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Section 304.11, IMC 2012 requires the installation of guards to protect personnel working on mechanical equipment within ten-feet of a roof edge. There is no exception in the mechanical code that allows the use of a tie-off system in lieu of guards. Submit an appeal to the building official to obtain permission to make the substitution. |
| 06/05/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/05/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 06/05/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/05/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/05/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 06/05/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/08/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved |