Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM03793
Parcel: 11306107B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03793
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Specify the materials to be used for the domestic water service to the addition and the section of the building sewer from the addition. Show how the separations of the water service and the building sewer are to be addressed. Reference: Sections 603.2, 605, and 702, IPC 2012.
2. Provide the rim elevation of the next upstream sanitary manhole and determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. (Note that section 3/A3.0 calls out the finished floor elevation for the existing building as 2371.90', not 2372.00' as shown on the site drawings.)
3. Provide secondary (overflow) roof drainage for the roof over the storage room (Room 103). Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.
4. Provide dimensions for the gutters along with the locations and dimensions of the downspouts. Reference: Sections 1106.1 and 1106.6, IPC 2012.
06/19/2015 ROBERT SHERRY WATER REVIEW Completed
06/19/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show how the minimum required outside air is to be introduced into room 103 (storage). Reference: Sections 403.2 and 403.2.2, IMC 2012.
2. Provide energy code compliance calculations (e.g. COMcheck) for the additions to the building envelope; use the climate zone for Tucson. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012
3. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.
4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
06/24/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/06/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING PLAN
REVIEW COMMENTS
Date: 7-7-15
Activity: T15CM03793
Address: 1301 E. Ft. Lowell
Applicant: William Ford

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

Sheet T1.0
1. Please clarify the maximum allowable area for type VB construction for an E occupancy. The plan indicates 12,000 maximum and Table 503 specifies 9,500.
Sheet G1.0
2. Demonstrate how the required exits on the east side of the building discharge to a public way without passing through the exit path of the required exit located on the south side of the building, 1027.
Sheet A1.2
3. When the primary use of the plumbing fixtures will be for the use of children, the fixtures must comply with ANSI A177.1 - 604.11
Sheet S1.0
4. The structural calculations indicate on sheet 28 that a 3'6" square footing is necessary. Please provide consistent information on the building plan, 107.2.1.
Sheet S2.0
5. Please clarify the support at each end of the beams supporting the east side of the proposed covered porch, 107.2.1.

If you have any questions please contact:

Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
07/07/2015 CTREVIL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed