Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T15CM03779
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/22/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 06/30/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide for the following; #1. The Ufer ground ( concrete encased electode ) for the service equipment is not optional as noted on the electrical riser detail Plan Sheet E2.1. Also provide for Water and Gas pipe bonding if applicable. NEC art. 250.50, 250.104. #2. Provide for Tamper Resistant, Arc Fault protection for outlets per NEC art. 210.12, 210.52, 406.12. #3. Full compliance with the Tucson Outdoor Lighting Code. |
| 07/13/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2012. 2. Provide underground facility tracer wires per ARS 40-360.22. 3. Provide fixture descriptions for all plumbing fixtures. Reference: Section 402, IPC 2012 and Section 107.2.1, IBC 2012. 4. If the showers do not have pre-fabricated receptors, provide details to show that the construction of the receptors complies with the requirements of Section 417.5.2, IPC 2012. 5. Provide shower control valves that comply with the requirements of Sections 424.3 and 424.5, IPC 2012. 6. Provide equipment data for the water heater. Reference: Section 107.2.1, IBC 2012. 7. Clarify the size of the return piping for the recirculated hot water on the plans: ½" or ¾". Reference: Section 107.2.1, IBC 2012. 8. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference: Section C404.4, IECC 2012. 9. Clarify the water pressure calculations. What was the basis for assuming the water pressure available at the property line? Verify that the pressure losses from the water meter and the reduced pressure backflow preventer are as determined by the manufacturers. How is the hot water recirculation pump contributing to the system pressure drop? Why is the total water fixture count used in the pressure loss calculations different from that determined in the plumbing fixture schedule? Reference: Section 604.1, IPC 2012. 10. What is the source of the fixture units used in the plumbing fixture schedule? Reference: Section 604.1, IPC 2012. 11. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2012. 12. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. the clothes washer). Reference: Section 604.9, IPC 2012. 13. Provide a full-open valve for the water service at the building entrance. Reference: Section 606.1(2), IPC 2012. 14. Show the inverts, cleanouts, and slope of the building sewer line on the drawing. Reference: Section 107.2.1, IBC 2012. 15. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. 16. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012. 17. Clarify the waste and vent riser diagram by showing each fixture just once (i.e. don't try to show both the plan view and the riser diagram at the same time). Reference: Section 107.2.1, IBC 2012. |
| 07/13/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. (Note that the description of the wall types on sheet A1.1 calls for R-19 batt insulation in the 2x4 exterior walls but R-13 batt insulation is noted elsewhere in the drawing set and in the HVAC load calculations.) Reference: Sections R101.4.3, R101.5, R103.2, and R401.2, International Energy Conservation Code 2012. 2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables R303.1.3 (1), R303.1.3 (2) and R303.1.3.(3), IECC 2012. Specify the required U-factors and Solar Heat Gain Coefficients (SHGC) for the fenestration and doors on the architectural drawings. Reference: Section R303.1.3, IECC 2012. 3. Show how the building envelope is to be constructed to limit the air leakage per the requirements of Section R402.4, IECC 2012. 4. Show the air leakage rating of the air handlers (ASHRAE Standard 193). Reference: Sections R103.2 and R403.2.2.1, IECC 2012. 5. Show that the two heat pumps are being installed in accordance with the conditions of their listings and the manufacturer's installation requirements (i.e. show that there is adequate maintenance space and clearance for air flow). Reference: Section 304.1, IMC 2012. 6. Show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference: 401.4, IMC 2012. 7. The balancing information on sheet M1.1 calls for 80 CFM of supply to each toilet room but only 50 CFM of exhaust (intermittent). Complete recirculation of ventilation air from toilet rooms is prohibited. Reference: Footnotes f and g, Table 403.3 and Section 403.2.1 (4), IMC 2012. 8. Provide sufficient dampers in the ductwork to ensure that the HVAC systems can be adjusted to distribute the required amount of ventilation air. Reference: Section 403.7, IMC 2012. 9. Provide an air balancing report prior to the final mechanical inspection to verify that the HVAC systems are capable of supplying and exhausting at least the minimum air flow rates called for in the design drawings. The balancing shall be performed by a qualified balancing contractor in accordance with the procedural standards of either the National Environmental Balancing Bureau (NEBB) or the Associated Air Balance Council (AABC). Reference: Section 403.7, IMC 2012. |
| 07/13/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/14/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | BUILDING PLAN REVIEW COMMENTS Date: 7-15-15 Activity: T15CM03779 Address: 5527 E. Hawthorne Applicant: Steve Macholtz This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval. General: 1. Please provide a sheet number for the site plan sheet and include it on the sheet index located on sheet T1.1. 2. Penetrations through a fire-rated wall assembly must comply with 714.3.2. Include manufacturer specifications on plan set for any fire stop systems on penetrations with brand, type and installation requirements. 3. Note: The draftstop indicated above the ceiling may be installed but is not a City of Tucson mandatory requirement since this project includes a full NFPA 13 sprinkler system, 718.4.3. 4. Provide details for the installation of accessible plumbing fixtures and elements including grab bars, 1102.1. Site Plan: 5. Provide one-hour fire-rated exterior walls where located within 10 feet of property lines, 602.1. 6. Please indicate the location of accessible parking and loading facilities, 1106.1, ANSI A117 501.1. 7. Indicate the running slope of walking surfaces and ramps along the accessible route, ANSI A117 403, 405. 8. Specify the location of detectable warnings between pedestrian and vehicular areas, ANSI A117 406.12. Sheet A1.1 9. Provide a shear wall attachment schedule on the building plan for each shear wall design, 1603.1. 10. Please indicate the location of the 30 minute fire separation between sleeping units. It is not clear whether the door to the restroom is part of this assembly or the wall between the restrooms, 310.6, 420.2. 11. Show the location of the attic access openings, 1209.2. 12. Specify which sleeping room(s) is the accessible unit and indicate where the bed and clear floor space is located, ANSI A117 1002.15. 13. Specify which bathroom is accessible and indicate how the plumbing fixture requirements are met, ANSI A117 601.1. Sheet A2.1 14. Please indicate the roof slope and roof covering materials located in the mechanical cove, 1503.1. 15. Specify the wall covering materials in the mechanical cove, 1408.4. 16. Provide an attic ventilation calculation and indicate the size and location of the vents required, 1203.2. Sheet A4.1 17. Provide details that meet the accessible kitchen requirements ANSI A117 606, 804, 902.4. Sheet S1.0 18. Provide a detail that indicates how the stucco weep screed for the exterior wall covering will be elevated 2 inches above the exterior paved surface where a zero-step entry has a floor elevation that is the same height on both sides of the wall, 2512.1.2. Sheet S2.0 19. Please clarify how the minimum one-hour fire-rating will be maintained for the exterior wall assembly with ventilated frieze boards, 705.10. Sheet E1.1 20. Specify how the means of egress will be illuminated at all times, 1006.1. If you have any questions please contact: Clayton Trevillyan, CBO 520.837.4913 Clayton.Trevillyan@tucsonaz.gov |
| 07/25/2015 | CPIERCE1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/29/2015 | CPIERCE1 | OUT TO CUSTOMER | Completed |