Permit Number: T15CM03703
Parcel: 117110170

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03703
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
06/03/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/03/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/03/2015 MARTIN BROWN FIRE REVIEW Approved
06/03/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/03/2015 ROBERT SHERRY WATER REVIEW Completed
06/03/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the tags for the water heaters; two WH-1 entries are shown in the specifications.
2. Provide an expansion tank for the mini-tank water heater.
3. Clarify the location of the standpipe for the t&p relief - indirect waste receptors may not be located within a cabinet.
06/03/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/10/2015 JASON GREEN ENGINEERING REVIEW Approved