Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03703
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/03/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/03/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
06/03/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/03/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/03/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/03/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
06/03/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the tags for the water heaters; two WH-1 entries are shown in the specifications. 2. Provide an expansion tank for the mini-tank water heater. 3. Clarify the location of the standpipe for the t&p relief - indirect waste receptors may not be located within a cabinet. |
06/03/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/10/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved |