Permit Number: T15CM03624
Parcel: 13728021B

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T15CM03624
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2015 JASON GREEN ENGINEERING REVIEW Reqs Change DATE: June 2, 2015
SUBJECT: Photovoltaic System
TO: SolarCity Corporation
REVIEWERS: Jason Green, CFM


SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the Site Plan for the installation of a photovoltaic system and does not recommend approval of the Site Plan at this time.

1) Revise the site plan to accurately show the property dimensions. The adjacent parcel should not be shown on this site plan. The plan should be for the subject property only, refer to the legal description for the east-west property boundary dimension.



If you have any questions, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services
06/04/2015 SSHIELD1 NPPO REVIEW Passed
06/04/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T15CM03624
926 W. Melridge Street
Residential (1st Review)

TRANSMITTAL DATE: June 4, 2015

The solar plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

Show only the parcel for this project.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/30/2015 CPIERCE1 BUILDING-RESIDENTIAL REVIEW Needs Review