Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03601
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/04/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/16/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Correct the plumbing calculations on sheet G1.03: the number of fixture units is to be determined using the occupant load of each sex, not the total number of occupants. The number of required fixtures shown in Table 2902.1, IBC 2012 is based upon the minimum fixtures required for each person or fraction of the number of persons. Since fractional fixtures cannot be installed, fractional numbers for fixtures shall also be rounded up to the next whole number. Based on a population of 58 males and 58 females, there is a total requirement of six water closets, not four. Provide separate facilities for each sex. Reference: Footnote (a), Table 2902.1 and Section 2902.2, IBC 2012. 2. Show that the installation of a "quench" system in lieu of a drinking fountain provides the required accessibility noted in Section 1109.5, IBC 2012 and Section 410.2, IPC 2012. 3. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. |
06/16/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012. |
06/16/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the sequence of operation for the restroom exhaust fans EF-1, EF-2, and EF-3 so that all of the air supplied to the restrooms will be exhausted (i.e. the restrooms shall be exhausted continuously while the building is being occupied). Reference: Sections 403.2.1 (4) and 403.3, IMC 2012. 2. The occupant load used to calculate the required ventilation is not necessarily the same as the furniture layout provided by the Architect. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2012 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2012. 3. Clarify the occupancy type used to calculate the required ventilation rate for each air conditioning zone. Reference: Section 403.3, IMC 2012. |
06/22/2015 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | Need Floodplain Use Permit for substantial improvement review. The FUP can be processed over the counter once all of the other Sections have completed the review. JG |
06/23/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Denied | While the electrical review for the current submittal is approved, due to the potential modifications necessary to address comments associated with the reviews of other disciplines the electrical workflow is denoted as denied in order to verify that those modifications will not adversely impact the electrical review. |
06/30/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | BUILDING PLAN REVIEW COMMENTS Date: 7-1-15 Activity: T15CM03601 Address: 8616 E. Broadway Blvd Applicant: Metro TED This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval. Sheet G1.02 1. Please specify the location of the accessible parking, 1106. 2. Indicate the accessible route from the public way and from the accessible parking spaces to the front door, 3411.6. Note: Additional accessibility features may need to be included if not already provided such as ramps in accordance with chapter 11. Sheet G1.03 3. Include information in code analysis regarding occupancy separation and fire-rated wall assemblies. Demonstrate previous use of tenant space as a B occupancy (no change in occupancy class) or specify the use of the adjoining tenant space and provide fire-rated assemblies accordingly, Table 508.4. 4. Please provide consistent information between the architectural page and the electrical layout regarding the location of the exit signage, 1011.1. 5. Clarify the proposed maximum occupant load or provide sufficient plumbing fixtures for the occupant load indicated, 2902. If you have any questions please contact: Clayton Trevillyan, CBO 520.837.4913 Clayton.Trevillyan@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/07/2015 | AROMERO4 | APPROVAL SHELF | Completed |
07/07/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |
07/07/2015 | AROMERO4 | REJECT SHELF | Completed |