Permit Number: T15CM03580
Parcel: 117120200

Address:
35 N 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T15CM03580
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 3; SHEET G1.2; IBC CODE INFORMATION: THE EXTERIOR NORTH WALL IS NOT A FIRE WALL (PER SECTION 706), BUT FALLS UNDER SECTION 705. IT IS REQUIRED TO BE A ONE HOUR RATED WALL PER TABLE 602. THE MAXIMUM AREA OF OPENINGS IS REGULATED BY TABLE 705.8. PLEASE VERIFY ON THE DRAWINGS THE OPENINGS IN THE NORTH WALL MEET THOSE REQUIREMENTS.
2. PREVIOUS COMMENT 4; SHEET G1.2; BASEMENT PLAN: THE MEASUREMENT REQUIREMENTS OF THE IBC SECTION 1016.3 INDICATE HORIZONTAL AND VERTICAL EGRESS TRAVEL PATHS, NOT DIAGONAL. PLEASE REVISE THE TRAVEL DISTANCE ON THE PLAN.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/10/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved; the structural calculations mention adding 2x4's to some trusses but no details are shown on the drawings that indicate how the ceilings are to be built or connected to the trusses. [Initial comment: Provide structural calculations for mounting the water heaters on the restroom ceilings to verify that the 50-gallon water heaters will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.]
2. Comment not resolved; the structural calculations mention adding 2x4's to some trusses but no details are shown on the drawings that indicate how the ceilings are to be built or connected to the trusses. [Initial comment: Provide structural calculations for mounting the water heaters on the bathroom ceilings to verify that the 30-gallon water heaters will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.]
08/11/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/19/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved