Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03576
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/29/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/29/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 06/01/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/01/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/01/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET T1.1; CODE REVIEW; SITE PLAN: THE CODE REVIEW INDICATES THE OFFICE AREA OF 2958 SF, WHILE THE SITE PLAN INDICATES 2978 SF. PLEASE CLARIFY. 2. SHEET T1.1; CODE REVIEW: PLEASE REVISE THE ELECTRICAL CODE EDITION TO 2011, AND REVISE THE PLUMBING CODE EDITION TO 2012. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 06/01/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/01/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/01/2015 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater plumbing. |
| 06/01/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/03/2015 | MARTIN BROWN | FIRE | REVIEW | Approved |