Permit Number: T15CM03575
Parcel: 128100810

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03575
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
05/29/2015 JASON GREEN ENGINEERING REVIEW Approved
06/01/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide IECC compliance for interior lighting.
06/01/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T1.1; CODE REVIEW: THE REFERENCE TO THE IPC SECTION 410.3 REQUIRING 0 DRINKING FOUNTAINS IS NOT CORRECT. THE IPC AND IBC (TABLE 2902.1, NOTE F) REQUIRES A HIGH/LOW DRINKING FOUNTAIN OR A SINGLE POINT OF USE WATER DISPENSER FOR OCCUPANT LOADS GREATER THAN 15. PLEASE REVISE THE DRAWING.
2. SHEET T1.1; CODE REVIEW: THE ELECTRICAL CODE SHOULD REFERENCE THE 2011 NEC, AND THE PLUMBING CODE SHOULD REFERENCE THE 2012 IPC. PLEASE REVISE.
3. SHEET A3.1; ACCESSIBLE MOUNTING HEIGHTS: ADD NOTES/DIMENSIONS FOR THE VERTICAL GRAB BAR PER THE ICC/ANSI FIGURE 604.5.1.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/01/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/03/2015 AROMERO4 MECHANICAL-COMMERCIAL REVIEW Needs Review
06/03/2015 AROMERO4 PLUMBING-COMMERCIAL REVIEW Needs Review
06/03/2015 AROMERO4 WATER REVIEW Needs Review
06/03/2015 AROMERO4 FIRE REVIEW Needs Review
06/03/2015 AROMERO4 WWM REVIEW Completed