Permit Review Detail
Review Status: Active
Review Details: REVISION - - 1ST
Permit Number - T15CM03510
Review Name: REVISION - - 1ST
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2015 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed | T15CM03510 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL NOTES: " Provide compliance with the 2012 International Fire Code 605.11.3.2.4 showing panels no higher than 3 feet below the ridge where panels are located. The only residential buildings excepted from this requirement are carports and similar open structures. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/10/2015 | ANY | APPROVAL SHELF | RECEIVED |