Permit Number: T15CM03479
Parcel: 141185840

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM03479
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2015 JASON GREEN ENGINEERING REVIEW Approved
05/26/2015 DAVID RIVERA ZONING REVIEW Approved
05/26/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1.Please provide for special inspection for Outdoor Ltg. Per sec. 106.2.1.
#2. Plans show 2 new meter pedistals, both designated as ' MP1' ? Please clarify.
Ref; IBC sec. 107.2.1, NEC atr. 110, 230, 408,
#3. Please provide a detail showing service pedistals, concrete pads, include complete grounding information.
05/29/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PLEASE PROVIDE STRUCTURAL CALCULATIONS AND DETAILS FOR THE LIGHT POLES. PROVIDE THE DETAILS ON THE DRAWINGS.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2015 AROMERO4 OUT TO CUSTOMER Completed