Permit Number: T15CM03459
Parcel: 13317064C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03459
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2015 DAVID RIVERA ZONING REVIEW Approved
05/22/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that the thermostat being relocated complies with the current energy code. Reference: Section C101.4.2, IECC 2012.
05/22/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/22/2015 ROBERT SHERRY WATER REVIEW Completed
05/22/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET TS1 (PROJECT LOCATION PLAN); PROJECT NARRATIVE: THE NARRATIVE INDICATES THIS TI IS ON THE FIRST FLOOR, WHILE THE LOCATION PLAN INDICATES THE THIRD FLOOR. PLEASE VERIFY.
2. SHEET TS1; DEFERRED SUBMITTALS: IT IS INDICATED THAT AN AUTOMATIC FIRE SUPRESSION SYSTEM WILL BE A DEFERRED SUBMITTAL FOR THIS PROJECT. PLEASE VERIFY IF THE SPRINKLER SYSTEM IS EXISTING.
3. SHEET A1; WALL TYPE DETAILS 3 AND 5: THE WALL BRACES ON THESE DETAILS REFERENCE THE IBC SECTION 1607.13. PLEASE REVISE TO 1607.14.
4. SHEET A1 (FLOOR PLAN); SHEET A2 (DOOR SCHEDULE): NEW DOOR 111 IS IN A RATED WALL (6A), BUT DOES NOT APPEAR TO BE A RATED DOOR. PLEASE VERIFY.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/22/2015 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
05/22/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/22/2015 LOREN MAKUS ENGINEERING REVIEW Approved
05/22/2015 MARTIN BROWN FIRE REVIEW Approved
05/22/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed