Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03382
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/21/2015 | ERIC NEWCOMB | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 05/21/2015 | ERIC NEWCOMB | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/21/2015 | ENEWCOM1 | WATER | REVIEW | Passed | |
| 05/21/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 05/21/2015 | ENEWCOM1 | WWM | REVIEW | Passed | |
| 05/21/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/21/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 06/10/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/11/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |