Permit Number: T15CM03299
Parcel: 133243700

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03299
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2015 STEVE SHIELDS ZONING REVIEW Approved
05/18/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch (lower case font also shall have a minimum height of 3/32"). Reference: Section 107.2.1, IBC 2012.
2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.
05/18/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/18/2015 JASON GREEN ENGINEERING REVIEW Approved
05/18/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
05/18/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the existing water and backflow preventer.
05/18/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the plumbing plans showing the installation of the new fixtures and the removal of the existing fixtures.
05/18/2015 KEN BROUILLETTE FIRE REVIEW Approved
05/18/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed