Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03299
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 05/18/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum height of 3/32-inch (lower case font also shall have a minimum height of 3/32"). Reference: Section 107.2.1, IBC 2012. 2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. |
| 05/18/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/18/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/18/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 05/18/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the existing water and backflow preventer. |
| 05/18/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the plumbing plans showing the installation of the new fixtures and the removal of the existing fixtures. |
| 05/18/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 05/18/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |