Permit Number: T15CM03251
Parcel: 110035860

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM03251
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 7-09-15
Activity: T15CM03251 2ND REVIEW
Address: 3925 E Ft. Lowell Rd #106/107
Applicant: Metro TED

PREVIOUS COMMENT:
2. Provide a minimum 1 hour fire-rated assembly for exterior walls located five (5) feet from imaginary property line, 602.1. Openings and glazing located in fire-rated assemblies must comply with section 716. Penetrations through a fire-rated wall assembly must comply with 714.3.2. Include manufacturer specifications on plan set for any fire stop systems on penetrations with brand, type and installation requirements.

Note: Please define all fire-rated doors and windows on the door and window schedules located on sheet A6.1. Include cut sheets on the construction drawings for the proposed fire-stop system for penetrations.