The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T15CM03251
Parcel: 110035860

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T15CM03251
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2015 KEN BROUILLETTE FIRE REVIEW Approved
05/27/2015 DAVID RIVERA ZONING REVIEW Approved
06/02/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/04/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/04/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/04/2015 ROBERT SHERRY WATER REVIEW Completed
06/15/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 6-15-15
Activity: T15CM03251
Address: 3925 E Ft. Lowell Rd #106/107
Applicant: Metro TED

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:
1. Indicate the location of the sidewalk from rear building exit (secondary exit) to the public way, 1027.5.

STRUCTURAL PLAN:
2. Provide a minimum 1 hour fire-rated assembly for exterior walls located five (5) feet from imaginary property line, 602.1. Openings and glazing located in fire-rated assemblies must comply with section 716. Penetrations through a fire-rated wall assembly must comply with 714.3.2. Include manufacturer specifications on plan set for any fire stop systems on penetrations with brand, type and installation requirements.
3. Clarify the section area of the steel stud lintels. The structural calculation indicates a 4x6 section area yet the plan shows a 6x6 lintel. Is a third 2x6 necessary as indicated in the cross section detail on the structural calculations?

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/26/2015 KROBLES1 OUT TO CUSTOMER Completed