Permit Number: T15CM03233
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03233
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2015 STEVE SHIELDS ZONING REVIEW Approved
05/14/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/14/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/14/2015 ROBERT SHERRY WATER REVIEW Completed
05/14/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/14/2015 RSHERRY1 WWM REVIEW Passed No water meter size change.
05/14/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
2. Provide tempered water for the lavatory using approved a device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater which is located above the fixture outlets. Reference: Section 504.2, IPC 2012.
05/14/2015 LOREN MAKUS ENGINEERING REVIEW Approved
05/14/2015 KEN BROUILLETTE FIRE REVIEW Approved
05/14/2015 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed