Permit Number: T15CM03203
Parcel: 12110005D

Address:
4770 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03203
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
05/13/2015 JASON GREEN ENGINEERING REVIEW Approved
05/13/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET D1.0; DEMOLITION FLOOR PLAN NOTES: NOTE 3 WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY.
2. SHEET A1.0; PARTITION DETAIL 1: PROVIDE A CALCULATION (ON THE DRAWINGS OR A SEPARATE SHEET) INDICATING THE 9' TALL INTERIOR PARTITION CAN RESIST THE HORIZONTAL LOAD REQUIRED FROM THE IBC SECTION 1607.14.
3. SHEET A1.0; FLOOR PLAN A: IN WAITING ROOM 100, AN ELEVATION X/A3.0 IS INDICATED. PLEASE REVISE.
4. SHEET A2.0; ELEVATION 5D: PLEASE PROVIDE A VERTICAL GRAB BAR PER THE ICC/ANSI FIGURE 604.5.1.
5. SHEET A2.0: PLEASE ADD DETAILS AND DIMENSIONS FOR WALL GRAB BARS AND PAPER DISPENSER PER THE ICC/ANSI FIGURE 604.5.1, FIGURE 604.5.2, AND FIGURE 604.7.
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/13/2015 MARTIN BROWN FIRE REVIEW Approved
05/13/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/14/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations to show that adequate ventilation is being provided. Reference: Section 403.2, IMC 2012.
05/14/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide for wiring methods, devices to comply with 517.13 NEC in patient treatment areas.
05/14/2015 ROBERT SHERRY WATER REVIEW Completed
05/14/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/14/2015 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.