Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03203
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/13/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/13/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET D1.0; DEMOLITION FLOOR PLAN NOTES: NOTE 3 WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY. 2. SHEET A1.0; PARTITION DETAIL 1: PROVIDE A CALCULATION (ON THE DRAWINGS OR A SEPARATE SHEET) INDICATING THE 9' TALL INTERIOR PARTITION CAN RESIST THE HORIZONTAL LOAD REQUIRED FROM THE IBC SECTION 1607.14. 3. SHEET A1.0; FLOOR PLAN A: IN WAITING ROOM 100, AN ELEVATION X/A3.0 IS INDICATED. PLEASE REVISE. 4. SHEET A2.0; ELEVATION 5D: PLEASE PROVIDE A VERTICAL GRAB BAR PER THE ICC/ANSI FIGURE 604.5.1. 5. SHEET A2.0: PLEASE ADD DETAILS AND DIMENSIONS FOR WALL GRAB BARS AND PAPER DISPENSER PER THE ICC/ANSI FIGURE 604.5.1, FIGURE 604.5.2, AND FIGURE 604.7. 6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/13/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/13/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/14/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide calculations to show that adequate ventilation is being provided. Reference: Section 403.2, IMC 2012. |
| 05/14/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide for wiring methods, devices to comply with 517.13 NEC in patient treatment areas. |
| 05/14/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/14/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/14/2015 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater plumbing. |