Permit Number: T15CM03202
Parcel: 137055300

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03202
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2015 DAVID RIVERA ZONING REVIEW Approved
05/13/2015 LOREN MAKUS ENGINEERING REVIEW Approved
05/13/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET D-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES AND VERBIAGE ON THE DEMOLITION PLAN.
2. SHEET D-1; KEY NOTE 10: PLEASE PROVIDE A NOTE ON THE DRAWINGS INDICATING HOW THE MAXIMUM 20% OF THE PROJECT COST WAS USED TO IMPROVE AN AREA OF PRIMARY FUNCTION (ACCESSIBILITY TO THE BUILDING, GRAB BARS IN THE RESTROOM, ETC.) PER THE IBC SECTION 3411.7.
3. SHEET A-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES AND VERBIAGE ON THE FLOOR PLAN AND CEILING PLAN.
4. SHEET A-1; FLOOR PLAN: NEW RACKS MUST BE SUBMITTED AS A DEFERRED SUBMITTAL TO THIS PROJECT. RACKS UP TO 6' TALL NEED NO FURTHER REQUIREMENTS. RACKS OVER 6' TALL UP TO 12" TALL REQUIRE A DETAIL ON THE DRAWINGS FOR THE CONNECTION TO THE FLOOR SLAB. RACKS OVER 12' TALL REQUIRE STRUCTURAL CALCULATIONS AND A DETAIL ON THE DRAWINGS FOR THE CONNECTION TO THE FLOOR SLAB.
5. SHEETS D-1 AND A-1: PROVIDE A NORTH ARROW ON THE PLANS.
6. SHEET A-1; FLOOR PLAN: IS THE SERVICE ROOM 101 ACCESSIBLE TO THE PUBLIC? CAN DOORS 2 AND 4 BE LOCKED? PLEASE VERIFY.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/13/2015 MARTIN BROWN FIRE REVIEW Approved
05/13/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/14/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/14/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/14/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this suite and the total water demand for that meter.
05/14/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Denied pending resolution of the building comments.
06/04/2015 AROMERO4 WWM REVIEW Completed