Permit Number: T15CM03192
Parcel: 107020150

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03192
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T1.0; EXITING PLAN: PLEASE REVISE THE EXIT ACCESS TRAVEL DISTANCES METHOD OF MEASUREMENT TO MATCH THE REQUIREMENTS OF THE IBC SECTION 1016.3 (HORIZONTAL AND VERTICAL EGRESS TRAVEL).
2. SHEET T1.0; WALL TYPES LEGEND: PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE WALL TYPE D (LOCATED BETWEEN GRIDS D AND E). THIS WALL IS SUPPORTED ONLY AT THE ROOF STRUCTURE AND AT THE FLOOR.
3. SHEET T1.0; SPRINKLER SYSTEM: PLEASE INDICATE ON THE DRAWINGS THE SPRINKLER SYSTEM SHALL MEET THE REQUIREMENTS OF THE IBC SECTION 903.3.1.1 USING AN NFPA 13 SYSTEM.
4. SHEET T1.0; SPRINKLER SYSTEM: PLEASE INDICATE ON THE DRAWINGS THE SPRINKLER SYSTEM SUPERVISION, ALARMS, AND MONITORING MEET THE REQUIREMENTS OF THE IBC SECTIONS 903.4, 903.4.1, AND 903.4.2.
5. SHEET T1.0; FLOOR PLAN: THE PULPIT AREA (KEYNOTE 9) MUST MEET THE REQUIREMENTS OF THE IBC SECTION 410.4. PLEASE INDICATE ON THE DRAWINGS THE CONSTRUCTION REQUIREMENTS ARE MET.
6. SHEET T1.0: PLEASE PROVIDE ON THE DRAWINGS THE CALCULATIONS FOR THE REQUIRED NUMBER OF PLUMBING FIXTURES PER THE IBC TABLE 2902.1.
7. SHEET T1.0: WHERE THE TOTAL NUMBER OF TOILET FIXTURES REQUIRED IS SIX OR MORE, AN ACCESSIBLE FAMILY TOILET IS REQUIRED PER THE IBC SECTION 1109.2.1. PLEASE VERIFY AND PROVIDE AS REQUIRED.
8. SHEET T1.0; OCCUPANT LOAD TABLE: IN THIS TABLE, IT APPEARS THE OCCUPANT LOAD FOR THE FELLOWSHIP HALL WILL NOT OCCUR CONCURRENTLY WITH THE LOAD IN THE SANCTUARY. PLEASE VERIFY THAT STATEMENT. THE ADJUSTED TOTAL OCCUPANT LOAD INDICATED ON THE DRAWINGS MUST INCLUDE AN APPEAL TO THE BUILDING OFFICIAL IF LESS THAN THE 928 TOTAL.
9. SHEET T1.0; KEYNOTE 6: PLEASE INDICATE ON THE FLOOR PLAN THE LANDINGS AT THE EXIT MEET THE REQUIREMENTS OF THE IBC SECTIONS 1008.1.5 AND 1008.1.6.
10. SHEET T1.0; FLOOR PLAN: PLEASE PROVIDE ON THE DRAWINGS THE HEADERS/LINTELS REQUIRED OVER THE NEW WALL OPENINGS ALONG WITH JAMB REQUIREMENTS.
11. SHEET T1.0; FLOOR PLAN: PLEASE VERIFY ON THE DRAWINGS THE MEANS OF EGRESS AND EXIT DISCHARGE MEET THE ILLUMINATION REQUIREMENTS OF THE IBC SECTION 1006, INCLUDING EMERGENCY POWER (INCLUDING SECTION 1011.6.3) AND ILLUMINATION LEVEL.
12. SHEET T1.0: PLEASE VERIFY ON THE DRAWINGS THE HANDRAILS AT RAMPS MEET THE REQUIREMENTS OF THE IBC SECTION 1012.



13. SHEET T1.0 (FLOOR PLAN); SHEET T2.0 (SECTION A): THE DEVELOPMENT PLAN (DP13-0245) INDICATES THE NORTH WALL OF THE BUILDING IS A FULL HEIGHT MASONRY WALL (TWO HOUR FIRE WALL) SINCE THE BUILDING IS ON THE PROPERTY LINE. SECTION A/T2.0 INDICATES A FULL HEIGHT METAL FRAMED WALL. PLEASE COORDINATE.
14. SHEET T1.0; FLOOR PLAN: THE BUILDING EXIT AT THE NORTHEAST CORNER DOES NOT APPEAR TO MEET THE CRITERIA OF THE IBC SECTIONS 1020.2.2 AND 1027.5. THERE DOES NOT APPEAR TO BE A DIRECT PATH TO THE PUBLIC WAY. PLEASE VERIFY. IF ACCESS TO A PUBLIC WALL CANNOT BE PROVIDED, VERIFY THE EXISTENCE OF A SAFE DISPERSAL AREA PER THE IBC SECTION 1027.5 AND INDICATE ON THE PLAN.
15. SHEET T1.0; FLOOR PLAN: THE BUILDING EXIT AT THE NORTHEAST CORNER DOES NOT APPEAR TO BE ACCESSIBLE. PLEASE VERIFY THE REMAINING THREE EXITS ARE ACCESSIBLE TO MEET THE IBC SECTION 1105.1 REQUIREMENTS. ON THE DRAWINGS, PROVIDE A NOTE INDICATING A SIGN WILL BE ADDED AT THIS EXIT THAT STATES THIS IS NOT AN ACCESSIBLE EXIT.
16. SHEET T1.0; FLOOR PLAN: THE BUILDING EXIT AT THE NORTHEAST CORNER DOES NOT APPEAR TO HAVE A LANDING THAT MEETS THE IBC SECTION 1008.1.6. PLEASE INDICATE THIS LANDING ON THE DRAWINGS.
17. SHEET T1.0; FLOOR PLAN: PLEASE VERIFY ON THE DRAWINGS THE EXITING WIDTH PER THE IBC SECTION 1028.2 FOR THE ASSEMBLY AREAS (SANCTUARY AND FELLOWSHIP HALL) IS MET.
18. SHEET T1.0; FLOOR PLAN: PLEASE VERIFY ON THE DRAWINGS THE WIDTH FOR AISLE EXITING PER THE IBC SECTION 1028.6 FOR THE ASSEMBLY AREAS IS MET.
19. SHEET T1.0; FLOOR PLAN: PLEASE VERIFY ON THE DRAWINGS THE TRAVEL DISTANCE AND COMMON PATH OF EGRESS TRAVEL PER THE IBC SECTIONS 1028.7 AND 1028.8 FOR ASSEMBLY AREAS ARE MET.
20. SHEET T1.0; FLOOR PLAN: PLEASE VERIFY ON THE DRAWINGS THE AISLE REQUIREMENTS PER THE IBC SECTION 1028.9 FOR ASSEMBLY AREAS ARE MET. INDICATE THE SEATING ON THE PLAN.
21. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/13/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved