Permit Number: T15CM03183
Parcel: 133291870

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03183
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/20/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: PROVIDE A CODE ANALYSIS ON THE DRAWINGS, INDICATING OCCUPANCY TYPE AND SF.
2. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR THE LATERAL ANALYSIS. DETERMINE FOUNDATION REQUIREMENTS (SIZE AND REINFORCING) AND ANCHOR REQUIREMENTS (SIZE, QUANTITY, AND EMBEDMENT).
3. GENERAL: PROVIDE A SITE PLAN INDICATING THE BUILDING LOCATION AND DIMENSIONS TO PROPERTY LINES AS REQUIRED.
4. GENERAL: PROVIDE BUILDING SPECIFICATIONS.
5. GENERAL: ADDITIONAL COMMENTS MAY BE INCLUDED IN SUBSEQUENT REVIEWS.
06/12/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/12/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Grounding detail on plan E-0 shows only one ground rod for grounding electrode. Please provide for a second ground rod ( supplemental ) or provide for a ground electrode resistance test to verify ground resistance less than 25 ohms.
Per NEC art. 250.53 A 2.
06/12/2015 LOREN MAKUS ENGINEERING REVIEW Approved
06/12/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a design for the water supply to the kiosk and the drainage from the kiosk.
06/12/2015 ROBERT SHERRY WATER REVIEW Reqs Change Show the size and location of the water meter and the backflow preventer.
06/16/2015 AROMERO4 ZONING REVIEW Needs Review
06/16/2015 AROMERO4 FIRE REVIEW Needs Review