Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03183
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 05/20/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. GENERAL: PROVIDE A CODE ANALYSIS ON THE DRAWINGS, INDICATING OCCUPANCY TYPE AND SF. 2. GENERAL: PROVIDE STRUCTURAL CALCULATIONS FOR THE LATERAL ANALYSIS. DETERMINE FOUNDATION REQUIREMENTS (SIZE AND REINFORCING) AND ANCHOR REQUIREMENTS (SIZE, QUANTITY, AND EMBEDMENT). 3. GENERAL: PROVIDE A SITE PLAN INDICATING THE BUILDING LOCATION AND DIMENSIONS TO PROPERTY LINES AS REQUIRED. 4. GENERAL: PROVIDE BUILDING SPECIFICATIONS. 5. GENERAL: ADDITIONAL COMMENTS MAY BE INCLUDED IN SUBSEQUENT REVIEWS. |
| 06/12/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/12/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Grounding detail on plan E-0 shows only one ground rod for grounding electrode. Please provide for a second ground rod ( supplemental ) or provide for a ground electrode resistance test to verify ground resistance less than 25 ohms. Per NEC art. 250.53 A 2. |
| 06/12/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/12/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide a design for the water supply to the kiosk and the drainage from the kiosk. |
| 06/12/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Show the size and location of the water meter and the backflow preventer. |
| 06/16/2015 | AROMERO4 | ZONING | REVIEW | Needs Review | |
| 06/16/2015 | AROMERO4 | FIRE | REVIEW | Needs Review |