05/20/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The use of a glass filler is acceptable provided that the cup dispenser is permanently mounted at an accessible location. [Initial comment: Provide a drinking fountain.]
05/20/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Correct and complete the ventilation calculations. Provide general exhaust for the classroom and shampoo area at 0.60 cfm/square foot. [Initial comment: Revise the ventilation calculations, using "beauty salon" instead of "classroom". AC-2 is also serving part of the same area. Note that general exhaust of 0.60 cfm/square foot is required for a beauty salon.]
05/20/2015 ROBERT SHERRY WATER REVIEW Completed
05/21/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: LOOKING AT THE OCCUPANCY LOAD, THE NUMBER ON THE EXIT PLAN DOES NOT AGREE WITH THE NUMBER IN THE CODE REVIEW CHECKLIST. THE CHECKLIST INDICATES 42 OCCUPANTS, WHILE THE EXIT PLAN INDICATES 46. PLEASE CLARIFY. THE GROSS SF SHOULD BE USED FOR THE BUSINESS AREAS (INCLUDING CORRIDORS, RESTROOMS, ETC.), AND THE NET SF CAN BE USED FOR THE CLASSROOM AREA. REVISE THE OCCUPANT LOAD ACCORDINGLY.