Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03177
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/20/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The use of a glass filler is acceptable provided that the cup dispenser is permanently mounted at an accessible location. [Initial comment: Provide a drinking fountain.] |
05/20/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Correct and complete the ventilation calculations. Provide general exhaust for the classroom and shampoo area at 0.60 cfm/square foot. [Initial comment: Revise the ventilation calculations, using "beauty salon" instead of "classroom". AC-2 is also serving part of the same area. Note that general exhaust of 0.60 cfm/square foot is required for a beauty salon.] |
05/20/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/21/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. GENERAL: LOOKING AT THE OCCUPANCY LOAD, THE NUMBER ON THE EXIT PLAN DOES NOT AGREE WITH THE NUMBER IN THE CODE REVIEW CHECKLIST. THE CHECKLIST INDICATES 42 OCCUPANTS, WHILE THE EXIT PLAN INDICATES 46. PLEASE CLARIFY. THE GROSS SF SHOULD BE USED FOR THE BUSINESS AREAS (INCLUDING CORRIDORS, RESTROOMS, ETC.), AND THE NET SF CAN BE USED FOR THE CLASSROOM AREA. REVISE THE OCCUPANT LOAD ACCORDINGLY. |