Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM03164
Parcel: 125170380

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03164
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
05/12/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/12/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/12/2015 JASON GREEN ENGINEERING REVIEW Approved
05/12/2015 ROBERT SHERRY WATER REVIEW Completed
05/12/2015 KEN BROUILLETTE FIRE REVIEW Approved
05/14/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/14/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/14/2015 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed