Permit Number: T15CM03162
Parcel: 103190230

Address:
2841 W GORET PL

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM03162
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM03162

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

ELEVATIONS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray tight to the roof sheathing or rigid board sealed to roof framing), R806.5. This condensation control provision is necessary for code compliance and may be layered with batt insulation for achieving the total required roof R-value.

PLUMBING PLANS:

1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Update the 105,000 BTU branch to the kitchen with 1" gas pipe.

MECHANICAL PLANS:

1. Provide whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3.

ELECTRICAL PLANS:

1. Show all garage receptacle outlets with GFCI protection, E3902.2. Include the ceiling receptacle on circuit #24.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2015 KROBLES1 OUT TO CUSTOMER Completed