Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T15CM03100
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2015 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | P&DS TRANSMITTAL FROM: Steve Shields, Lead Planner PROJECT: T15CM03100 1450 E. El Atajo Permit Existing Porch Cover TRANSMITTAL: May 12, 2015 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 7'-11" the required perimeter yard setback to the east property line is 6'-0" proposed setback is 1'-0". |
| 05/12/2015 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 07/06/2015 | AROMERO4 | ENGINEERING | REVIEW | Needs Review | |
| 07/06/2015 | AROMERO4 | BUILDING-RESIDENTIAL | REVIEW | Needs Review |