Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM03060
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/04/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | ADDITIONAL COMMENTS CONCERNING THE DEMOLITION ON THE PROJECT: 1. SHEET D1.0; BASEMENT DEMOLITION PLAN: KEYNOTE 35 INDICATES AN EXISTING DOOR TO BE REMOVED AND TO PREPARE THE WALL FOR INFILL. KEYNOTE 40 IN THE SAME AREA INDICATES TO REMOVE A BRICKED IN DOOR/WINDOW AND PREPARE FOR A NEW OPENING. PLEASE CLARIFY. 2. SHEET A2.0; BASEMENT PLAN: KEYNOTE 17 IN THE SOUTH WALL INDICATES A NEW OPENING AND TO PROVIDE A LINTEL. THE BASEMENT DEMOLITION PLAN ON SHEET D1.0 (KEYNOTE 40) INDICATES AN EXISTING DOOR/WINDOW OPENING THAT IS BRICKED IN AT THIS SAME LOCATION. IS A NEW LINTEL REQUIRED, OR IS THERE AN EXISTING LINTEL OVER THE EXISTING OPENING? PLEASE CLARIFY. 3. SHEET A2.0; BASEMENT PLAN: ARE THE SECTION CUTS 1/A5.0 AND 2/A5.0 CUT IN THE WRONG DIRECTION? PLEASE VERIFY. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. THE PREVIOUS COMMENTS WERE BACK CHECKED AND APPROVED. |
| 06/05/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |