Permit Number: T15CM03060
Parcel: 12405049A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03060
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2015 KEN BROUILLETTE FIRE REVIEW Approv-Cond 1. THE FUTURE USE OF THE BUILDING WILL REQUIRE FIRE SPRINKLERS AND FIRE ALARM SYSTEMS
05/18/2015 LOREN MAKUS ENGINEERING REVIEW Approved
05/21/2015 STEVE SHIELDS ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Steve Shields, Lead Planner

PROJECT:
T15CM03060
Illegal Pete's
Window replacement

TRANSMITTAL: May 6, 2015


COMMENTS: the following comments are relative to an application for Historic Review and Design Development Option (DDO) (UDC 3.11.1).

This site is located in the HC-1 zone (UDC 4.7.20). A retail use is permitted in this zone (Table 4.8-4) Subject to Use Specific Standard 4.9.9.B.3 and 4.9.13.O

Historic review is required for exterior window replacement.
05/22/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET S2.2
1. Please provide structural calculations for beams B1, B4, B6 and B7.
2. Please provide structural calculations for column C2.
4. In calcs, (PPG 9) need to show beams B6, B7 and B8 on key plan.
5. In calcs, (PPG 18) need to show beam B7. on key plan.
6. Please show calculations of existing joists that require 2-2x8 addition as per notes 25 and 42 and 1-2x8 as per note 26.
SHEET S2.2
7. Please provide calculations that show analysis of the existing joists that require 2-2x8 addition at the roof plan.
8. Also, show notes 41 and 42 on the plan.
END OF REVIEW
05/28/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify that this building is subject to the requirements of the 2012 IECC. Reference: Section C101.4.2, IECC 2012.
2. If the building is to comply with the prescriptive requirements of the 2012 IECC, clarify how the mass walls are to have continuous insulation (R-5.7ci) added to the mass walls. Reference: Table C402.2, IECC 2012.
3. If the operable glazed fenestration for the building is to comply with the prescriptive requirements of the 2012 IECC, show how the replacement windows will be built to have a maximum U-factor of 0.65 BTU/h*ft2*ºF (e.g. double pane glass). Reference: Section C303.1.3, IECC 2012.
05/28/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed NO Electrical
05/28/2015 ROBERT SHERRY WATER REVIEW Completed
05/28/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed