Permit Number: T15CM02871
Parcel: 13324005F

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T15CM02871
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please clarify the following:
#1. The general notes for the electrical scope of work on plan sheet A3 seem to conflict with plan sheet E1.0. In order to clarify this, please indicate on the electrical floor plans all devices, outlets, fans, luminaires, that are existing to remain, new, relocated, replaced, and, designated or assigned circuiting. Also to be reflected on all associated panel schedules including load calc's for each phase.
#2. All new lighting, receptacles, fans, including circuiting, panel designations for such to be clearly shown on the submittal documents. Engineered or performed by a licensed registrant, not "at the electrical contractors discretion".
Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
Ref: IBC sec.107.1, NEC art.90, 300, 408.
06/02/2015 ROBERT SHERRY WATER REVIEW Reqs Change Comment not addressed. [Initial comment: Provide the size of the water meter serving this building, the total water demand it sees and the serial number of the meter.]
06/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: Provide material standards for all plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2012.]
06/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012.]
2. Comment not addressed. [Initial comment: Show how the modified A/C units are to obtain return air.]
06/16/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET TS1; PROJECT DRAWING INDEX: PLEASE REVISE THE DRAWING INDEX AS REQUIRED.
2. SHEET TS1; APPLICABLE CODES: PLEASE REVISE THE NEC TO THE 2011 EDITION AND REMOVE THE EXISTING BUILDING CODE FROM THE LIST.
3. SHEET TS1; PROJECT CODE REVIEW: PLEASE ADD ON THIS SHEET THE PLUMBING FIXTURE CALCULATIONS.
4. SHEET TS1; PROJECT CODE REVIEW: PLEASE REVISE THE OCCUPANT LOADS ACCORDING TO THE IBC TABLE 1004.1.2. PLEASE ADVISE AS TO WHICH ROOMS ARE INCLUDED IN THE OFFICE CALCULATION (744 SF), THE LOUNGE AREA (351 SF), THE WORKOUT ROOM (289 SF), AND STORAGE (322 SF). THE LAUNDRY ROOM AND RECEPTION ARE BOTH CONSIDERED ASSEMBLY AREAS.
5. SHEET A1.0; FLOOR PLAN: PLEASE SEPARATE THE DEMOLITION PLAN AND THE FLOOR PLAN. IT IS DIFFICULT TO DIFFERENTIATE THE TWO ON THIS PLAN.
6. SHEET A1.0; FLOOR PLAN: PLEASE ADD A PROJECT DESCRIPTION OF THE PREVIOUS USE AND THE NEW USE. IT APPEARS THE PREVIOUS USE MAY HAVE BEEN AS AN APARTMENT (FULL KITCHEN, BATH TUB). IS THIS NEW OCCUPANCY A CHANGE?
7. SHEET A1.0; FLOOR PLAN: THE DOORS DENOTED 24 AND 25 DO NOT MEET THE MANEUVERING CLEARANCE PER THE ICC/ANSI FIGURE 404.2.3.2(a).
8. SHEET A1.0; FLOOR PLAN: THE DOOR DENOTED 25 DOES NOT MEET THE MANEUVERING CLEARANCE PER THE ICC/ANSI FIGURE 404.2.3.2(a) FOR THE 18" CLEARANCE.
9. SHEET A1.0; FLOOR PLAN: THE DOORS DENOTED 23 AND 39 DO NOT MEET THE MANEUVERING CLEARANCE PER THE ICC/ANSI FIGURE 404.2.3.2(a) FOR THE 18" CLEARANCE.
10. SHEET A1.0; KEYNOTE 34: PROVIDE AN ELEVATION OF THE COUNTER ON THE DRAWINGS.
11. SHEET A1.0; KEYNOTE 27: PROVIDE AN ELEVATION OF THIS AREA ON THE DRAWINGS (INCLUDING THE SINK).
12. SHEET A1.0; KEYNOTE 20: PROVIDE AN ELEVATION OF THIS AREA ON THE DRAWINGS (INCLUDING THE SINK).
13. SHEET A1.0; KEYNOTE 35: PROVIDE AN ELEVATION OF THIS COUNTER ON THE DRAWINGS.
14. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.