Permit Number: T15CM02871
Parcel: 13324005F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM02871
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2015 STEVE SHIELDS ZONING REVIEW Approved
04/30/2015 LOREN MAKUS ENGINEERING REVIEW Approved
05/01/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide a complete panel schedule with load calc's. Include assigned circuiting for lighting and receptacles.
05/01/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012.
2. Show how the modified A/C units are to obtain return air.
05/01/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
05/01/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this building, the total water demand it sees and the serial number of the meter.
05/01/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide material standards for all plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2012.
05/01/2015 MARTIN BROWN FIRE REVIEW Approved
05/01/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/19/2015 FRODRIG2 WWM REVIEW Completed