Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/30/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/30/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
05/01/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Provide a complete panel schedule with load calc's. Include assigned circuiting for lighting and receptacles. |
05/01/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012. 2. Show how the modified A/C units are to obtain return air. |
05/01/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
05/01/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter serving this building, the total water demand it sees and the serial number of the meter. |
05/01/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide material standards for all plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2012. |
05/01/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/01/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/19/2015 | FRODRIG2 | WWM | REVIEW | Completed |