Permit Number: T15CM02869
Parcel: 132082240

Address:
1991 E AJO WY

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM02869
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 6: DETAIL 3 STILL INDICATES THE DIAGONAL BRACE AT THE TOP OF THE PARTITION WALL NEEDS 2 #6 TEK SCREWS TO THE CEILING. THIS WAS NOT CHANGED PER THE PREVIOUS REVIEW COMMENT.
2. PREVIOUS COMMENT 13: A RACKING PLAN IS REQUIRED ANY TIME RACKS ARE INCLUDED IN A PROJECT (FOR EGRESS AND EXITING PURPOSES). PLEASE PROVIDE ON THE PLANS. FOR RACKS OVER 6' TALL UP TO 12' TALL, A DETAIL IS REQUIRED ON THE DRAWINGS FOR THE CONNECTION OF THE RACK TO THE FLOOR. PLEASE PROVIDE.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/08/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
06/08/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/08/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations for the suite shown on the drawings (i.e. the same size suite shown on the drawings, with glazing, with ventilation air and no infiltration). Clarify the source of the internal loads. [Initial comment: Clarify the selection of the proposed heat pump. The load calculations show a total cooling load of 12,537 BTUH and a heating load of 16930 BTUH but the capacity of the heat pump is shown as 34 MBH cooling and 31 MBH heating.]