Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM02869
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/30/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/30/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
05/01/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
05/01/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the selection of the proposed heat pump. The load calculations show a total cooling load of 12,537 BTUH and a heating load of 16930 BTUH but the capacity of the heat pump is shown as 34 MBH cooling and 31 MBH heating. |
05/01/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
05/01/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/01/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/01/2015 | RSHERRY1 | WWM | REVIEW | Passed | No water meter size change. |
05/01/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
05/05/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1. Please locate the 200 amp loadcenter on the floor plan. #2. Show panel feeder conductor sizes and types. |