Permit Number: T15CM02869
Parcel: 132082240

Address:
1991 E AJO WY

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM02869
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2015 STEVE SHIELDS ZONING REVIEW Approved
04/30/2015 LOREN MAKUS ENGINEERING REVIEW Approved
05/01/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/01/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the selection of the proposed heat pump. The load calculations show a total cooling load of 12,537 BTUH and a heating load of 16930 BTUH but the capacity of the heat pump is shown as 34 MBH cooling and 31 MBH heating.
05/01/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
05/01/2015 ROBERT SHERRY WATER REVIEW Completed
05/01/2015 MARTIN BROWN FIRE REVIEW Approved
05/01/2015 RSHERRY1 WWM REVIEW Passed No water meter size change.
05/01/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/05/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1. Please locate the 200 amp loadcenter on the floor plan.
#2. Show panel feeder conductor sizes and types.