Permit Number: T15CM02776
Parcel: 124040010

Address:
1448 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM02776
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2015 DAVID RIVERA ZONING REVIEW Approved
04/28/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the attachment of fan coil FC-12 to the building structure.
04/28/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1.Please provide circuiting for FC# 12 (Panel Sch.).
#2. Residential kitchen countertop receptacles require GFI protection and a min. of two dedicated circuits per NEC, IBC.
#3.Tamper resistant receptacles in lounge.
#4. Locate loadcenters on floorplan.
04/28/2015 ROBERT SHERRY WATER REVIEW Completed
04/28/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Needs Review
04/28/2015 RSHERRY1 WWM REVIEW Passed No water meter size change.
04/28/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/28/2015 JASON GREEN ENGINEERING REVIEW Approved
04/28/2015 MARTIN BROWN FIRE REVIEW Approved
04/28/2015 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed