Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM02735
Parcel: 141186040

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T15CM02735
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2015 KEN BROUILLETTE FIRE REVIEW Approved
05/08/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change GENERAL
1. Please provide structural calculations and details for the following:
a. Roof top mounted HVAC equipment
b. Wall mounted water heater
2. Please provide a site plan.
SHEET A-0
3. Change the 2012 IEC to the 2011 NEC
SHEET A-1
4. As per section 2903.3.1 of the 2012 IBC, toilet rooms may not be accessed through a storage room.
SHEET A-6
5. At detail 6/A6 shows a roof hatch ladder atop the ceiling structure of the toilet room. Please provide the fokllowing:
a. A building section through the toilet room showing the roof, toilet ceiling, first floor, and all toilet walls, ceiling ladder, hatch, suspended water heater and details.
b. Provide a structural framing plan and structural calculations and details.
c. Show access to the ceiling structure of the toilet room.
SHEET S-1
5. The foundation key plan is a mirror image of the foundation plan on this sheet. Please rectify.
END OF REVEIW
05/11/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The plumbing notes on sheet M-2 indicate that the plumbing design has been done per the 2012 International Plumbing Code. Revise the references to the 2006 UPC on the drawing to show the applicable sections of the 2012 IPC. Reference: Section 101.4, IBC 2012, as amended by the City of Tucson.
2. Provide a site plumbing plan showing the size and slope of the building sewer and the proposed location of the yard hydrant (this information is not shown on the civil drawings). Reference: Section 107.2.1, IBC 2012.
3. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
4. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
5. Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2012.
6. Specify the expansion tank to be used with the proposed water heater. Reference: Section 607.3, IPC 2012.
7. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference: Section C404.4, IECC 2012.
8. Provide a sign for the freeze-proof yard hydrant located at grade stating "Caution, Nonpotable water, Do Not Drink." Reference: Section 608.7, IPC 2012.
9. The freeze-proof yard hydrant located on the roof does not have a below-grade stop-and-waste valve and thus may not require the installation of backflow preventer; no backflow preventer is shown on sheet M-2 but a note calls for the pipe supplying the hydrant to be labeled as "non-potable." Resolve the disparity between the installation shown and the "non-potable" note. Reference: Section 608.7, IPC 2012.
10. Provide complete roof drainage calculations and plans. Reference: Sections 1101, 1106 and 1108, IPC 2012. Clarify the design for the building storm drain shown on sheets A-6 and M-1; the civil plans do not indicate the presence of a storm sewer system but call for three splash blocks located along the Northwest wall of the building. If horizontal rainwater piping is to be used, indicate the minimum slope of the pipe. Reference: Section 1101.2, IPC 2012.
05/11/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The 2012 International Energy Compliance Code is the relevant energy code for this project, correct note 3 of the mechanical notes on sheet M-1.
2. Revise the energy code analysis for the building envelope, coordinating the building components used in the analysis with those shown on the drawing (i.e. use the wall construction shown on the drawings or change the drawings to match the COMcheck components) and provide the supporting documentation for the U-factors used in COMcheck. Reference: Section C303.1, IECC 2012, as amended by the City of Tucson.
3. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.
4. Coordinate the HVAC system shown on the drawings (2 10-ton packaged heat pumps, EER = 11.0) with the system noted in COMcheck (2 10-ton DX units with gas heat, EER = 11.5). Reference: Section C303.1.3, IECC 2012.
5. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
6. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
7. Clarify how excess outside air relief from the building is to be accomplished (e.g. during economizer operation). Reference: Section C403.3.1.1.4, IECC 2012.
05/11/2015 ROBERT SHERRY WATER REVIEW Reqs Change Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water and are typically installed outside of the building, directly after the water meter. Provide the size of both the water meter and the backflow preventer. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
05/12/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please show full compliance with the Tucson Outdoor Lighting Code. Include color temperature output.
05/12/2015 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
Principal Planner

PROJECT: T15CM02735
10240 E Old Vail Road
Building Plans

TRANSMITTAL DATE: May 12, 2015

DUE DATE: May 26, 2015

COMMENTS:

01. Zoning has reviewed the building plans but cannot approve them at this review. Zoning could compare the buildings plans to the development package because the latest revision has not been scanned and a copy of the approved DP was not included in the building package.

02. Zoning will review the building plans on the next submittal and compare them to the approved DP as it pertains to the zoning review purview of the building plans. Include a copy of the approved DP with the next submittal.

03. Additional zoning comments may be forthcoming based on the review of the building plans when compared to the approved DP.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
05/22/2015 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/16/2015 KROBLES1 OUT TO CUSTOMER Completed