Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM02627
Parcel: 12502029A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM02627
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2015 ENEWCOM1 FIRE REVIEW Needs Review
04/21/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/21/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/21/2015 ROBERT SHERRY WATER REVIEW Completed
04/21/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A2.01; DEMOLITION PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE VERBIAGE.
2. SHEET A2.02; DEMOLITION PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE VERBIAGE.
3. SHEET P2.01; DETAIL 1: THE FIRST NOTE INDICATES TO SUPPORT THE WATER HEATER FROM THE STRUCTURE ABOVE PER THE STRUCTURAL PLANS. PLEASE PROVIDE THOSE STRUCTURAL PLANS.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/21/2015 LOREN MAKUS ENGINEERING REVIEW Approved
04/21/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a design for connecting the mounting shelf for the water heater to the building structure along with structural calculations to show that the water heater is safely supported. Reference: Section 301.2, IPC 2012.
2. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012.
04/21/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/27/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
04/28/2015 KROBLES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2015 KROBLES1 OUT TO CUSTOMER Completed