Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM02622
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T15CM02622
608 N. Treat Avenue
Residential (1st Review)

TRANSMITTAL DATE: April 23, 2015

The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

Zoning cannot approve the building plan until a plot plan has been submitted

Once the above comment is addressed Zoning is willing to provide an over-the-counter review. Call or email to schedule this appointment.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/24/2015 JASON GREEN ENGINEERING REVIEW Reqs Change Site plan required along with recordation of the final plat information. Once this is done ENG will provide an over the coutner approval. JG
04/28/2015 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 4-28-15
Activity: T15CM02622
Address: 608 N. Treat
Applicant: Desert Wolf Drafting

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code and local amendments. In order to facilitate a shorter back check time, we request that you provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Correct notations referring to regulations adopted by Pima County.
2. Clarify the location of the proposed studio remodel on the site plan. Note: converting a non-habitable space to habitable space will include the conditions for all new residences.
3. The Tucson Water policy adopted 7/13/12 limits the maximum demand for a 5/8" water meter to 15 GPM. Provide a water meter sized for the proposed water demand. Reference Tables P2903.6 and P2903.6 (1), IRC 2012.
4. Include a gas bond on the electrical riser diagram, E3607/8.
5. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.
6. Kitchens require two or more 2O-amp small appliance circuits to serve countertop receptacles. Such circuits shall be GFCI protected and shall not serve other rooms (except breakfast areas, pantries, etc.), E3901.3.
7. Show receptacle outlets at wall spaces 2' or more so that no point along the wall (excluding door openings) is more than 6' from a receptacle outlet, E3901.2.
8. Show receptacle outlets at each kitchen counter space wider than 12" so that no point along the wall line is more than 24" from a receptacle outlet, E3901.4.1.
9. Condensation control is required for the unvented roof assembly method. Specify an air-impermeable rigid insulation material sealed tight to the roof sheathing or spray applied closed cell foam to a minimum value of R5, R806.5.

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2015 KROBLES1 OUT TO CUSTOMER Completed