Permit Number: T15CM02588
Parcel: 137055250

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T15CM02588
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2015 MARTIN BROWN FIRE REVIEW Approved
04/24/2015 FRODRIG2 COMMUNICATIONS REVIEW Approved APPROVED PER JEFFREY SELIGMAN. LETTER SENT TO RECORDS.
05/05/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/12/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T-2: PROVIDE NOTES ON THIS SHEET FOR THE GEOTECHNICAL INVESTIGATION REPORT. INCLUDE SITE PREPARATION REQUIREMENTS, EXCAVATION REQUIREMENTS, ALLOWABLE BEARING VALUES, FOUNDATION TYPES, ETC.
2. STRUCTURAL CALCULATIONS (MAT FOUNDATION); GEOTECHNICAL INVESTIGATION REPORT (SHEET 9): THE ALLOWABLE BEARING PRESSURE INDICATED IN THE CALCULATIONS (7.50 KSF) DOES NOT AGREE WITH THE ALLOWABLE SOIL BEARING CAPACITIES LISTED IN THE SOIL REPORT. PLEASE CLARIFY.
3. GENERAL: ON THE DRAWINGS, PROVIDE A DETAIL OR SECTION OF THE MONOPOLE, INDICATING MANUFACTURER'S SPECIFICATIONS, AND ANY BOLTED OR WELDED CONNECTIONS REQUIRED WITHIN THE POLE LENGTH. INCLUDE BASE PLATE AND ANCHOR BOLT REQUIREMENTS (PER THE MANUFACTURER'S CALCULATIONS). THESE ARE CURRENTLY INDICATED IN THE CALCULATIONS BUT SHOULD ALSO BE SHOWN ON THE DRAWINGS.
4. GENERAL: ON THE DRAWINGS, PLEASE PROVIDE DETAILS OF THE ALTERNATE FOUNDATIONS (AS SHOWN IN THE CALCULATIONS).
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/15/2015 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2015 KROBLES1 OUT TO CUSTOMER Completed