Review Details: COMMERCIAL - TI

Permit Number - T15CM02576
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2015 STEVE SHIELDS ZONING REVIEW Approved
04/17/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/17/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/17/2015 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size and serial number of the water meter supplying this tenant improvement.
2. Provide the total water demand served by the water meter.
04/17/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/17/2015 JASON GREEN ENGINEERING REVIEW Approved
04/17/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise detail 204 to show a full-way valve downstream of the check valve for the sump pump. Reference: Section 712.2, IPC 2012.
1. Revise detail 204 to show that the pump waste connection to the drainage system complies with the requirements of Section 712.3.5, IPC 2012.
04/17/2015 MARTIN BROWN FIRE REVIEW Approved
04/17/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/20/2015 KROBLES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2015 KROBLES1 OUT TO CUSTOMER Completed