Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM02576
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/17/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/17/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/17/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Provide the size and serial number of the water meter supplying this tenant improvement. 2. Provide the total water demand served by the water meter. |
| 04/17/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/17/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/17/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise detail 204 to show a full-way valve downstream of the check valve for the sump pump. Reference: Section 712.2, IPC 2012. 1. Revise detail 204 to show that the pump waste connection to the drainage system complies with the requirements of Section 712.3.5, IPC 2012. |
| 04/17/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/17/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/20/2015 | KROBLES1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/20/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |