Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM02554
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/16/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/17/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1.Please provide a complete one line diagram, include voltage, phase, feeder sizes and types, indicate what is existing or new. #2. Show full compliance with the Tucson Outdoor Lighting Code. #3. Indicate new or existing for the outside light fixtures. If new, include them on the fixture schedule. |
| 04/17/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 04/17/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1; FLOOR PLAN: PER THE IBC SECTION 3411.7, A MAXIMUM OF 20% OF THE PROJECT COST MUST BE APPLIED TO THE PROJECT TO IMPROVE ACCESSIBILITY. PLEASE INDICATE ON THE DRAWING THIS ANALYSIS. |
| 04/17/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/17/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/17/2015 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater plumbing. |
| 04/17/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/17/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |