Review Details: RESUBMITTAL - TI ALL
Permit Number - T15CM02553
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 07/06/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the COMcheck Envelope Compliance analysis to show the roof as an attic roof with metal framing and R38 cavity insulation. Clarify the wall construction; the wall sections on sheet A6.4 show only part of each wall having continuous insulation and that is about R-5, not R-13. Also, the floor plan on sheet A1.0 shows the two end walls furred in with R-13 cavity insulation but this is not indicated on the envelope compliance certificate. [Second comment: This comment has not been resolved. The Envelope Compliance Certificate still calls for "Efficient HVAC Performance" (C406.2, IECC 2012) but both the Electrical Compliance Certificate and the Mechanical Compliance Certificate call for "Reduced Interior Lighting power".] [Initial comment: The Envelope Compliance Certificate indicates that the "Additional Efficiency Package Requirements" noted in COMcheck is to consist of "Efficient HVAC Performance" (C406.2, IECC 2012). Coordinate the Mechanical Compliance Certificate with the Envelope Compliance Certificate. Reference: Section C401.2, IECC 2012.] |
| 07/07/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/22/2015 | AROMERO4 | ZONING | REVIEW | Needs Review |