Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T15CM02546
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please clarify one line diagram to include new panel 'A' ,configuration,and provide correct feeder, conduit ,conductor sizes and types for 100 amp OCPD. Plan Sheet 'E3'. Ref; NEC art. 310, 408.4, IBC 107.2.1. |
| 05/14/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/14/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/14/2015 | RSHERRY1 | WWM | REVIEW | Passed | No water meter size change. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/14/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |