Permit Number: T15CM02546
Parcel: 115180180

Address:
1520 N 15TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM02546
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2015 MARTIN BROWN FIRE REVIEW Approved
04/16/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/16/2015 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/27/2015 JASON GREEN ENGINEERING REVIEW Approved
04/27/2015 DAVID RIVERA ZONING REVIEW Approved
05/04/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change How much outside air does the furnace supply to the building? There is currently a deficit of 410 CFM if the existing evaporative cooler is not running. Reference: Section 508, IMC 2012.
05/04/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide panel schedules for all panels new and existing, complete one line diagram, include new panel 'A'.
05/04/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/14/2015 KROBLES1 WATER REVIEW Needs Review
05/14/2015 KROBLES1 WWM REVIEW Needs Review