| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/16/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/16/2015 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/27/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/27/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/04/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | How much outside air does the furnace supply to the building? There is currently a deficit of 410 CFM if the existing evaporative cooler is not running. Reference: Section 508, IMC 2012. |
| 05/04/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide panel schedules for all panels new and existing, complete one line diagram, include new panel 'A'. |
| 05/04/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/14/2015 | KROBLES1 | WATER | REVIEW | Needs Review | |
| 05/14/2015 | KROBLES1 | WWM | REVIEW | Needs Review |