Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM02479
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/14/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/14/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
04/14/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G1.0; PROJECT CODE INFORMATION: THE ANSI A117.1 IS LISTED AS THE 2003 EDITION. PLEASE REVISE TO THE 2009. 2. SHEET G1.0; PROJECT CODE INFORMATION (PLUMBING FIXTURES): PER TABLE 2902.1, A SERVICE SINK IS REQUIRED. PLEASE REVISE THE DRAWING. 3. SHEET G1.0; PROJECT CODE INFORMATION: THE TABLE INDICATES A BATHTUB/SHOWER. PLEASE VERIFY WHERE THIS IS LOCATED. 4. SHEET G1.1; MEANS OF EGRESS: THE TABLE INDICATES THREE EXITS ARE PROVIDED. PLEASE VERIFY. 5. SHEET G1.1; LIFE SAFETY PLAN: PLEASE PROVIDE A NORTH ARROW ON THE PLAN. 6. SHEET G1.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE VERBIAGE. 7. SHEET A1.0; FLOOR PLAN: DOOR 100 (KEY NOTE 14) IS NOTED AS A SLIDER DOOR. VERIFY ON THE DRAWINGS THIS DOOR MEETS THE REQUIREMENTS OF SECTION 1008.1.4.3. 8. SHEETS A1.0, A2.0, AND A3.0: PLEASE PROVIDE A NORTH ARROW ON THE PLANS. 9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
04/14/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/15/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
04/15/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide a plumbing design and specifications for the installation of the new sink and a plumbing design for the relocation of the drinking fountain. |
04/15/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size and serial number of the existing water meter along with total demand served by the water meter. |
04/15/2015 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | 1. SHEET G1.0; PROJECT CODE INFORMATION: THE TABLE INDICATES A BATHTUB/SHOWER. PLEASE VERIFY WHERE THIS IS LOCATED. 2. SHEET G1.1; MEANS OF EGRESS: THE TABLE INDICATES THREE EXITS ARE PROVIDED. PLEASE VERIFY. 3. SHEET G1.1; LIFE SAFETY PLAN: PLEASE PROVIDE A NORTH ARROW ON THE PLAN. 4. SHEET A1.0; FLOOR PLAN: DOOR 100 (KEY NOTE 14) IS NOTED AS A SLIDER DOOR. VERIFY ON THE DRAWINGS THIS DOOR MEETS THE REQUIREMENTS OF SECTION 1008.1.4.3. SHEETS A1.0, A2.0, AND A3.0: PLEASE PROVIDE A NORTH ARROW ON THE PLANS. |
04/16/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | No emergency or egress lighting on plan, see note for electrical on cover sheet. |
04/30/2015 | KROBLES1 | WWM | REVIEW | Needs Review |